JUMO IMAGO 500
The manufacturing facilities and laboratories described in this section belong to JUMO. Contact IMAGO for equipment selection and supply in Kazakhstan.
Type 703590
Table of Contents
What does "*****" mean in the text?
If this error message appears, there are several possible reasons.
The following points need to be checked:
- Is the sensor (or input signal) connected correctly?
- Is the sensor faulty or is the input signal outside the measurement range?
- Is the analog input configured correctly?
How to run the automatic configuration function of the program controller?
The prerequisites for running the autotuning function JUMO IMAGO 500 are that the device is in the basic state and autotuning is enabled at the configuration level.
The output to be optimized must be set correctly (e.g. relay/analog output/solid state). Refer to Operating Instructions B 703590 "Controller 1 (2...4) > Automation".
Activating the Exit/Hand button for > 2 seconds switches the program controller to “Guidance Mode”. Use UP/DOWN to enter the required value for the set point and confirm with ENTER.
Activating buttons
produces
A button that can be used to start autotuning and stop it again. Using this softkey/button combination only optimizes the channel that has been selected for display.
How to change the set point value for a program controller in basic status?
To change the set point value for a program controller in basic status, follow these steps:
First press softkey
And then softies
That one over there.
A button will then appear that can be used to change the set point in the base status.
How to determine the date and time?
If it is necessary to set the date and time, this can be done either directly on the Imago 500, in the menu item “Configuration > Device data > Date and time”, or in the “Setup” section under the menu item “Extras > Date and time”.
The date and time are transmitted independently of the data transmission.
How can I set the sampling time?
The sampling time can be set in the “Settings” program, in the “Device Data” menu item.
The time 50, 150 or 250 milliseconds can be selected according to the application.
The actual sampling time that will be obtained may differ from the specified sampling time.
On the Imago 500 you can see the true sampling time in the menu item “Menu > Configuration Level > Device Data > System Sampling Time”.
This system sampling time cannot be programmed directly, but can only depend on the number of functions to be performed and the number of controllers.
How to configure user level?
The custom level is an additional level that will only be visible when you configure it. Up to 8 application-specific parameters can be shown here and edited at this level.
In Setup, under the menu item Display - User Level, you can select settings for the user level by entering addresses and defining specific client names for them.
For Float parameters you need to take the corresponding address +1
(e.g. limit comparator for threshold Al 1, address 0x026F +1 = 0x0270)
Note: This only applies to version 162.02.05 and includes
How to change the device language?
Changing the device language must be done in two steps.
At the first stage, the required language is selected and transferred to the device using Settings and Device Assistant "Edit" hardware.
At the second stage, the required language is selected for the element. "Extras > Device Text Library" and transferred to the device using the "Transfer" button.
This change will only take effect after the device is turned off and then on again.
How to change the unit of measurement?
In the standard version, the unit of measurement is set to °C. To select another unit in the Setup program, choose the relevant Analog value under Controller pics.
In the "Unit" section, the required unit of measurement can be entered in the "Text" item.
How can I enable device options?
There are several device options (Math, Controller 3+4, C-level, Recording) that can be enabled through Setup using a release code.
To be able to access these options, the device must be online. In Settings, go to the Extras menu in the taskbar, and then to Turn on device options.
Activating “Read code” opens an additional window in which the necessary parameters are marked:
You will be provided with a release code, which you can enter in the appropriate field using the "Enable" button.
Be careful! The code number may include a mathematical sign.
How can I program a gradient inside a program?
Time-dependent programming can be implemented using Imago 500. If a gradient is required, then the rate of change must be converted to give a value for the time period.
If, for example, a given point is to change from 10°C to 100°C at a rate of 5°C per minute, then the following conversion is required:
Setpoint change 90 °C / 5 °C per minute = 18 minutes for full ramp.
How to enable program options?
Similar to device options, there are a number of program options (Startup, Teleservice, Program Editor) that can be enabled for the installer.
In the menu item “Extras” - “Enable program parameters” you can enter the license number to enable the function you need.
You can obtain a licence number through IMAGO; the licence terms are clarified with the manufacturer:
Telephone: +7 708 327 8770
How long can I record measurement data using Startup?
The maximum recording time is limited to 24 hours. The recording duration does not depend on the number of channels used for recording. If the recording period has reached, a message will appear.
How can I suppress the error message PROFIBUS-DP ERROR if the interface PROFIBUS is not yet in use?
If IMAGO 500 is equipped with an interface PROFIBUS that is not already in use, the error message “PROFIBUS-DP ERROR” will appear on the display.
This error message can be suppressed by entering the device address PROFIBUS "0" directly from the IMAGO 500 keys.
From version 162.03.xx 3.00(J) above, you can also use PC to set the device address PROFIBUS to “0”.
How can I quickly make configuration changes using the Setup program?
Changes to settings in Imago 500 can be made faster using the Setup program if you do not need to transfer all the data, but only the data for the changed partition.
To do this, Imago 500 and the Setup program must be “Online”.
In the dialog area, use the right mouse button to click on the field you want to change, and then select the Edit Display Online menu item.
The currently valid settings will be read and displayed. When you finish editing and exit this menu item, the modified data for this section will be automatically transferred to Imago 500.
How can I start recording?
Recording is a device option that must be enabled to be used.
Recording will start as soon as this feature is enabled and the device is connected.
You can select the required signals (eg process value, set point, control deviation, etc.) either through the setup program or directly from the controller in the "Record" menu item. These signals will then be subsequently recorded on the display, just like on a regular recorder. The recorded time span depends on the sampling rate (which is adjustable) and can vary from approximately 12 hours to a maximum of 24 hours.